Introduction

Main Features

  • Robust stainless steel housing
  • Intrinsically safe version (LCIE 02 ATEX 6133X)
  • Available with optional Marine approval (Bureau Veritas Marine)

Application

  • Chemical
  • Pneumatic
  • Energy
  • Shipbuilding
  • Industrial gas

Measuring ranges and overpressure safety

Pressure in mbar

Pressure range 0 ... 25
0 ... 40
0 ... 60 0 ... 100
0 ... 160
0 ... 250
0 ... 400
0 ... 600
Over pressure 110 275 500 1000
Burst pressure 200 500 1000 2000

Pressure in bar

Pressure range -1 ... 0 -1 ... 0.6 0 ... 1 0 ... 1.6 -1 ... 1.5 0 ... 2.5 -1 ... 3 0 ... 4 -1 ... 5 0 ... 6 -1 ... 15 0 ... 16 -1 ... 24 0 ... 25 -1 ... 39 0 ... 40 0 ... 60 0 ... 100 0 ... 160 0 ... 250 0 ... 400 0 ... 600
Over pressure 3 4 8 12 32 50 80 120 200 320 500 600 800
Burst pressure 6 7 12 18 48 75 120 180 300 480 600 800 1000

Technical Specifications

Measuring principle   Thick film on ceramic  
Measuring ranges -1 ... 0 bar up to 0 ... 600 bar
Type of pressure   Relative / Absolute
Accuracy (20 °C)   ≤ ± 0.3% FS (BFSL)
(linearity, hysteresis and repeatability according Best Fit Straight Line) ≤ ± 0.6% FS (BFSL) for P ≤ 60 mbar and P= 600 bar
Error of zero point ≤ ± 1% FS
Error of span ≤ ± 1% FS
Zero thermal drift  ≤ ± 0.60% FS/10 K (P ≤ 1 bar) ≤ ± 0.25% FS/10 K (P > 1 bar)
Span thermal drift ≤ ± 0.15% FS/10 K (P ≤ 1 bar) ≤ ± 0.15% FS/10 K (P > 1 bar)
Long term stability 0.2 % FS / Year
Response time (10 … 90%)  ≤ 3 ms
Process connections See page 3