Baumer Flush Diaphragm Pressure Transmitter
Fully welded pressure transmitter with flush membrane and touch screen
- Programmable by touch screen
- Cavity-free process connection
- Resistant to all conventional CIP cleaning media
- Compact installation from G 1/2 A
- Optionally available with relay outputs
- Absolute pressure, relative pressure and vacuum measurement
- Easy and full programmable with FlexProgrammer 9701
An all stainless steel construction with flush diaphragm connection makes these transmitters ideally suited for measurements on viscous and heavy fluids suchs as paint, pulp and paper, and most uses in the refrigeration field. Hydraulic connections : G 1/2, G 3/4, G 1, 1/2 NPT
Measuring Ranges
Pressure range |
compound |
-1+0.6(1) |
-1+1.5(2) |
-1+3 |
-1+5 |
-1+9 |
-1+15 |
-1+24 |
-1+39 |
— |
— |
— |
— |
— |
— |
pressure |
1.6(1) |
2.5(2) |
4 |
6 |
10 |
16 |
25 |
40 |
60 |
100 |
160 |
250 |
400 |
600 |
|
Measurement range |
1.75 |
2.75 |
4,4 |
6,6 |
11 |
17.6 |
27.5 |
44 |
66 |
110 |
176 |
275 |
440 |
660 |
|
Max. over pressure |
3 |
4 |
8 |
12 |
20 |
32 |
50 |
80 |
120 |
200 |
320 |
500 |
600 |
800 |
|
Burst pressure |
6 |
7 |
12 |
18 |
30 |
48 |
75 |
120 |
180 |
300 |
480 |
600 |
800 |
1000 |
Technical Specifications (20 °C)
Attribute | Value |
---|---|
Measuring Range | -1 … 400 bar |
Min. Measuring Span | 0.05 bar |
Max. Measuring Span | 401 bar |
Pressure Type | Absolute Relative (gauged) |
Standard Error of Measurement (BFSL) | 0.04 % FSR , up to 2:1 turndown ratio 0.1 % FSR , up to 4:1 turndown ratio Including non-linearity, hysteresis and non-repeatability according BFSL For turndown, multiply this value by the applied turndown ratio |
Max. Measuring Error | ± 0.1 % FSR , up to 2:1 turndown ratio ± 0.25 % FSR , up to 4:1 turndown ratio Including zero-point and span error, nonlinearity (by terminal base line), hysteresis and non-repeatability (EN 61298-2) For turndown, multiply this value by the applied turndown ratio |
Temperature Coefficient | ≤ 0.05 % FSR/10 K , measuring span ≤ 0.05 % FSR/10 K , zero point |
Compensated Temperature Range | -40 … 85 °C |
Long Term Stability | ≤ 0.1 % FSR/a , IEC 770 6.3.2 |
Max. Turndown Ratio | 10 : 1 |
Rise Time (10 ... 90 %) | ≤ 0.3 s |
Sample Time | ≤ 0.3 s |
Power-up Time | < 10 s |